Read the reefer nameplate before you choose the power source. Most ISO reefers in the United States need 460 volts, 3-phase, 60 Hz.

Running power is in kilowatts. Compressor startup draws a surge several times higher. Size the breaker and the generator for the surge, not only for the running load. Carrier OptimaLINE specifications are one published example of the 460-volt supply. The plate on your unit governs.

Read the nameplate first

Record the rated voltage, the frequency, the full-load amps, and the inrush. Confirm 460 volts, 3-phase, 60 Hz. Note a dual-voltage listing if the plate has one. Some units also list 380 volts at 50 Hz. U.S. sites usually use 460 volts at 60 Hz.

Size for the surge

Running power changes with the setpoint and the weather. Do not copy a kilowatt number from a different unit.

For a three-phase estimate of running current:

amps = kilowatts × 1000 / (√3 × volts × power factor)

Use the rated power, the voltage, and the power factor from the plate. The startup surge is higher than that current. Size the breaker and the generator for the surge.

Choose shore power or a genset

Shore power is quiet and is often the cheaper supply to run. Many U.S. yards do not have a 460-volt, 3-phase receptacle. Confirm the service before the reefer is ordered.

A diesel genset is the usual fallback. Size it in kilowatts for the startup surge, and ask the supplier for the motor-starting rating. For cargo that cannot warm up, plan a second genset or a transfer arrangement, and a fueling routine.

An electric-standby arrangement is the third option when the unit can run on grid power at the site and on its own supply on the road.

Use the receptacle rules

46 CFR Subpart 111.79 requires a reefer receptacle to have an interlock or a disconnect nearby, plus a sign. The receptacle must be rated for circuit-breaking service.

For a circuit that supplies only one appliance, the cited rule limits the overcurrent device to 150 percent of the appliance rating, or 15 amps, whichever is greater. The appliance must meet UL or an equivalent standard. Motor loads need a separate check. The article points to this Coast Guard appliance-circuit text.

Do this before the unit arrives

  • Read the nameplate. Record voltage, full-load amps, and inrush.
  • Confirm that the service is 460 volts, 3-phase, and that the feeder has the capacity.
  • Have an electrician calculate voltage drop for the real cable length. Select the conductor from that result and the NEC tables.
  • Rate the cable and the connector for the voltage and the current, and for outdoor, wet, cold, and abrasive use.
  • Book the electrician and the permit review before you order.
  • Run a loaded test for 2 to 4 hours. Get the sign-off before you load cargo.

A longer cable loses voltage. A motor that starts through an undersized or overlong cable can stall or trip.

Expect a larger box to run longer

A 40-foot reefer has more air and more wall area than a 20-foot reefer. The compressor tends to run longer to hold the same setpoint. Size does not set the kilowatts by itself. Insulation and the setpoint do.

Hot weather raises the power draw. Confirm capacity and dimensions on the unit's own specifications.

Conexwest can supply the reefer. Ask for the rated voltage, the full-load amps, and the inrush for that unit before you size the supply. Related size notes are in the cold-storage capacity guide and the 40-foot reefer dimensions.

Questions

What powers a reefer?

Electricity, usually 460 volts, 3-phase, 60 Hz. The supply can be shore power, a diesel genset, or an electric-standby arrangement. Read the nameplate.

How many kilowatts does a reefer need?

Use the nameplate. Running kilowatts change with the setpoint and the weather. Size the breaker and the generator for the startup surge.

What is the payload of a 40-foot reefer?

It varies by unit. Read the CSC plate. Do not use a published chart in place of that plate.